Evaporator low temperature protection (T2)

Vitocal 100-SDLCLRC

What is going on

Compressor frequency is limited when the indoor coil temperature gets low, which can happen in cooling or drying.

Likely causes

  • Indoor coil temperature T2 too low

Check in this order

  1. If T2 is below 32°F (0°C), the compressor stops and restarts when T2 reaches 41°F (5°C).
  2. If T2 is between 32°F and 39.2°F (0°C to 4°C), the frequency drops to a lower level.
  3. If T2 is between 39.2°F and 44.6°F (4°C to 7°C), the compressor holds the current frequency.
  4. If T2 is above 44.6°F (7°C), the frequency is not limited.

Applies to: DLCLRC indoor coil

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-S DLCLRC service instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.