Evaporator low temperature protection (T2)
What is going on
Compressor frequency is limited when the indoor coil temperature gets low, which can happen in cooling or drying.
Likely causes
- Indoor coil temperature T2 too low
Check in this order
- If T2 is below 32°F (0°C), the compressor stops and restarts when T2 reaches 41°F (5°C).
- If T2 is between 32°F and 39.2°F (0°C to 4°C), the frequency drops to a lower level.
- If T2 is between 39.2°F and 44.6°F (4°C to 7°C), the compressor holds the current frequency.
- If T2 is above 44.6°F (7°C), the frequency is not limited.
Applies to: DLCLRC indoor coil
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-S DLCLRC service instructions, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.