Viessmann · Heat pump troubleshooting
Evacuating and charging the refrigerant system
What is going on
Deep vacuum method to remove air and moisture from the refrigerant tubes and indoor coil. Target is 500 microns. Always break vacuum with dry nitrogen. Never use the compressor as a vacuum pump.
Check in this order
- Tighten all flare nuts fully. Connect the manifold gauge charge hose to the charge port of the low side service valve.
- Connect the charge hose to the vacuum pump.
- Fully open the low side of the manifold gauge.
- Start the vacuum pump and evacuate using the triple evacuation method.
- When evacuation is complete, fully close the low side of the gauge and stop the pump.
- Disconnect the charge hose from the low side service valve charge port.
- Fully open service valves B and A.
- Tighten the valve caps securely.
- If line length is over 25 ft (8 m), add refrigerant as specified in the piping table.
Applies to: DLCURA outdoor units with indoor coil and refrigerant tubing
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCURA Service Manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.