Viessmann · Heat pump troubleshooting

Evacuate and charge the refrigerant system

Vitocal 100-S

What is going on

Deep vacuum procedure with triple evacuation. Use a vacuum pump that reaches 500 microns and a gauge that reads accurately at that level. Never use the compressor as a vacuum pump.

Check in this order

  1. Tighten all flare nuts fully and connect the manifold charge hose to the low side service port.
  2. Connect the other charge hose to the vacuum pump.
  3. Fully open the low side of the manifold gauge.
  4. Start the pump and evacuate to 500 microns, then run it 15 more minutes.
  5. Close the service valves and shut off the pump.
  6. Break the vacuum with dry nitrogen to 2 psig, then hold 10 minutes so the nitrogen absorbs moisture.
  7. Repeat the evacuation and nitrogen steps as shown in the triple evacuation chart.
  8. After the final evacuation, fully close the low side gauge and stop the pump.
  9. Add refrigerant per Table 10 if line length is over 25 ft (8 m).
  10. Disconnect the charge hose from the low side port.
  11. Fully open service valves B and A.
  12. Tighten all service valve caps.

Applies to: DLCSRB outdoor units, all sizes

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCSRB Service Manual, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.