Viessmann · Heat pump troubleshooting

Enquiry display: fan speed, EXV opening, running time, stop causes

Vitocal 100-SDLCLRC

What is going on

Other enquiry items shown on the service display, with the conversion rules.

Check in this order

  1. Fan speed display 0 = OFF, 1 = low, 2 = medium, 3 = high, 4 = turbo for some large motors.
  2. For some small motors the display is 14 to FF (hex) and the fan speed range is 200 to 2550 RPM.
  3. Actual fan RPM = display value converted to decimal, then multiplied by 10.
  4. EXV opening actual value = display value converted to decimal, then multiplied by 2.
  5. Compressor continuous running time shows 0 to 255 minutes.
  6. Compressor stop cause shows 0 to 99 in decimal. Consult the engineering reference for the meaning.

Applies to: DLCLRC enquiry mode

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-S DLCLRC service instructions, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.