Viessmann · Heat pump troubleshooting
Enquiry display: fan speed, EXV opening, running time, stop causes
What is going on
Other enquiry items shown on the service display, with the conversion rules.
Check in this order
- Fan speed display 0 = OFF, 1 = low, 2 = medium, 3 = high, 4 = turbo for some large motors.
- For some small motors the display is 14 to FF (hex) and the fan speed range is 200 to 2550 RPM.
- Actual fan RPM = display value converted to decimal, then multiplied by 10.
- EXV opening actual value = display value converted to decimal, then multiplied by 2.
- Compressor continuous running time shows 0 to 255 minutes.
- Compressor stop cause shows 0 to 99 in decimal. Consult the engineering reference for the meaning.
Applies to: DLCLRC enquiry mode
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-S DLCLRC service instructions, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.