Viessmann · Heat pump troubleshooting
Ductwork design and installation
What is going on
Ductwork must follow ACCA Manual D or local code. Keep duct inside conditioned space where possible. Attic duct needs extra insulation and must not be undersized or dusty.
Likely causes
- Undersized return air causing poor performance and blower pulsation
- Attic ducts without enough insulation losing heating and cooling capacity
- Dust from construction entering the system and fouling the air coil and condensate drain
Check in this order
- Design the duct system to ACCA Manual D or local code, sized for High Speed airflow.
- Install ductwork inside the conditioned space to limit heat loss or gain.
- In an attic, use a low-profile duct laid on the ceiling joists and cover it with 6-8 in (150-200 mm) of insulation.
- Use flex duct from the supply grille back six feet and line the first six feet of supply and return duct with acoustic insulation.
- Make all turns as smooth as possible.
- Use a high-efficiency air filter and tell the owner that most filters need monthly attention.
- Do not run the unit during construction or remodeling; this voids the warranty.
- When attaching ductwork, make sure screws do not penetrate and damage the air coil.
Applies to: Vitocal 100-WA, all models
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA installation, service and operating instructions, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.