Weil-McLain · Heat pump troubleshooting
DHW function on the ECO HP
What is going on
The ECO HP has no adjustable DHW settings. When the EVU contacts close, the unit runs in DHW mode, targeting the highest outlet water temperature it can reach. DHW takes priority over a heating call and runs until the call is removed. In Type A systems, the Max On Time is set in the Unity 2.0 control and limits the DHW call before heating priority runs. In Type B and C systems, the DHW-priority zone panel (such as the Weil-McLain Thermostat Interface Unit) has a fixed 1 hour timer, after which heating zones can run.
Check in this order
- Do not look for a DHW setting on the ECO HP; adjust Max On Time in the Unity 2.0 control for Type A systems.
- For Type B and C systems, allow for the fixed 1 hour DHW-priority timer on the zone panel.
Applies to: ECO HP domestic hot water operation
More heat pump guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO HP Heat Pump – Application Guide, p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.