Weil-McLain · Heat pump troubleshooting

DHW function on the ECO HP

ECO HP

What is going on

The ECO HP has no adjustable DHW settings. When the EVU contacts close, the unit runs in DHW mode, targeting the highest outlet water temperature it can reach. DHW takes priority over a heating call and runs until the call is removed. In Type A systems, the Max On Time is set in the Unity 2.0 control and limits the DHW call before heating priority runs. In Type B and C systems, the DHW-priority zone panel (such as the Weil-McLain Thermostat Interface Unit) has a fixed 1 hour timer, after which heating zones can run.

Check in this order

  1. Do not look for a DHW setting on the ECO HP; adjust Max On Time in the Unity 2.0 control for Type A systems.
  2. For Type B and C systems, allow for the fixed 1 hour DHW-priority timer on the zone panel.

Applies to: ECO HP domestic hot water operation

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO HP Heat Pump – Application Guide, p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.