Deep vacuum evacuation with a vacuum pump

Vitocal 100-SDLCLRC

What is going on

Evacuate the refrigerant tubes and indoor coil to a deep vacuum to remove air and moisture before charging.

Check in this order

  1. Tighten all flare nuts fully.
  2. Fully open all service valves.
  3. Connect the manifold charge hose to the charge port of the low side master service valve so all circuits evacuate together.
  4. Connect the charge hose to the vacuum pump.
  5. Fully open the low side of the manifold gauge.
  6. Start the vacuum pump and pull down to 500 microns.
  7. Close the low side of the manifold gauge and stop the pump once evacuation is complete.
  8. Disconnect the charge hose from the low side service valve charge port.
  9. Tighten the service valve caps securely.

Applies to: DLCLRC outdoor units with R410A

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-S DLCLRC service instructions, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.