Decommissioning and refrigerant recovery
What is going on
Recovery and decommissioning need a technician familiar with the equipment. Take a refrigerant and oil sample first if reuse may be needed.
Check in this order
- Confirm electrical power is available, then isolate the system electrically.
- Take oil and refrigerant samples before starting, if analysis may be needed.
- Pump the system down if possible. If not, fit a manifold to recover from several points.
- Use recovery equipment and cylinders approved for flammable refrigerant, with calibrated scales.
- Put the cylinder on the scales before recovery starts.
- Do not fill cylinders above 80% of volume with liquid.
- Do not exceed the cylinder's maximum working pressure, even briefly.
- Remove full cylinders and equipment from site promptly and close all isolation valves.
- Do not mix refrigerants in recovery units or cylinders.
- Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
- Label the equipment as decommissioned and emptied, with date and signature. Add a flammable refrigerant label if applicable.
Applies to: Vitocal 100-AW AM2V
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.