Viessmann · Heat pump troubleshooting

Decommissioning and refrigerant recovery

Vitocal 100-AW

What is going on

Recovery and decommissioning need a technician familiar with the equipment. Take a refrigerant and oil sample first if reuse may be needed.

Check in this order

  1. Confirm electrical power is available, then isolate the system electrically.
  2. Take oil and refrigerant samples before starting, if analysis may be needed.
  3. Pump the system down if possible. If not, fit a manifold to recover from several points.
  4. Use recovery equipment and cylinders approved for flammable refrigerant, with calibrated scales.
  5. Put the cylinder on the scales before recovery starts.
  6. Do not fill cylinders above 80% of volume with liquid.
  7. Do not exceed the cylinder's maximum working pressure, even briefly.
  8. Remove full cylinders and equipment from site promptly and close all isolation valves.
  9. Do not mix refrigerants in recovery units or cylinders.
  10. Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
  11. Label the equipment as decommissioned and emptied, with date and signature. Add a flammable refrigerant label if applicable.

Applies to: Vitocal 100-AW AM2V

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 11. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.