Viessmann · Heat pump troubleshooting

Current loop (S line) communication fault, no code shown

Vitocal IND-A

What is going on

Diagnosis of the S current loop between indoor and outdoor units. Normal reading: DC voltage between N/L2 and S alternates between positive and negative. A reading fixed near 0 or always positive points to a fault.

Likely causes

  • Wiring fault between indoor and outdoor units
  • Wiring fault between terminals and PCBs
  • Short circuit in a high-voltage component (4-way valve, heater, fan)
  • Short circuit in the electronic expansion valve coil
  • Faulty IPM board, main PCB, indoor PCB or outdoor PCB

Check in this order

  1. Power off, then restart the unit 2 minutes later and check whether the error disappears.
  2. Measure DC voltage between N/L2 and S black probe to S, red probe to N/L2.
  3. If the value is fixed near 0 or always positive, check the wiring between indoor and outdoor units.
  4. Check the wiring from the outdoor terminal to the outdoor PCB and between PCBs.
  5. Check the wiring from the indoor terminal to the indoor PCB.
  6. Check whether the power LED is on.
  7. Unplug each high-voltage component on the main PCB (4-way valve, heater, AC fan) and check its resistance for a short.
  8. Replace any short-circuited component and the main PCB.
  9. Unplug the electronic expansion valve and check the DC 5 V and 12 V supply to the main PCB.
  10. Check the AC voltage at L and N output to the IPM board; it should match the power input.
  11. Check the DC 5 V and 12 V from the IPM board to the main PCB.
  12. Replace the IPM board, the main PCB, the EEV coil, or the indoor or outdoor PCB as the checks indicate.

Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 18-19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.