Viessmann · Heat pump troubleshooting
Current loop (S line) communication fault, no code shown
What is going on
Diagnosis of the S current loop between indoor and outdoor units. Normal reading: DC voltage between N/L2 and S alternates between positive and negative. A reading fixed near 0 or always positive points to a fault.
Likely causes
- Wiring fault between indoor and outdoor units
- Wiring fault between terminals and PCBs
- Short circuit in a high-voltage component (4-way valve, heater, fan)
- Short circuit in the electronic expansion valve coil
- Faulty IPM board, main PCB, indoor PCB or outdoor PCB
Check in this order
- Power off, then restart the unit 2 minutes later and check whether the error disappears.
- Measure DC voltage between N/L2 and S black probe to S, red probe to N/L2.
- If the value is fixed near 0 or always positive, check the wiring between indoor and outdoor units.
- Check the wiring from the outdoor terminal to the outdoor PCB and between PCBs.
- Check the wiring from the indoor terminal to the indoor PCB.
- Check whether the power LED is on.
- Unplug each high-voltage component on the main PCB (4-way valve, heater, AC fan) and check its resistance for a short.
- Replace any short-circuited component and the main PCB.
- Unplug the electronic expansion valve and check the DC 5 V and 12 V supply to the main PCB.
- Check the AC voltage at L and N output to the IPM board; it should match the power input.
- Check the DC 5 V and 12 V from the IPM board to the main PCB.
- Replace the IPM board, the main PCB, the EEV coil, or the indoor or outdoor PCB as the checks indicate.
Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 18-19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.