Connect desuperheater to DHW tank
What is going on
Piping layout for the desuperheater loop to the DHW tank, including drain and check valves.
Check in this order
- Turn off power or fuel to the DHW tank and close the cold water supply valve.
- Drain the tank through the drain connection, opening a nearby faucet or relief valve to speed draining.
- Remove the drain fitting after draining.
- Install isolation ball valves and two drain valves so the pump can be serviced without draining the tank.
- Install a horizontal swing check valve to prevent tank overheating.
- Use metal fittings within 12 in (300 mm) of the desuperheater tee.
- Use mechanical fittings at a plastic (Marathon) tank; do not solder or braze near it.
- Match copper pipe size to the unit fittings; if 1 in (25 mm) copper is used, reduce it as close to the tank as possible.
- Never use plastic fittings between the tank and the unit.
- Follow the tank manufacturer's installation instructions.
Applies to: Vitocal 100-WA with DHW tank
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.