Viessmann · Heat pump troubleshooting

Condenser high temperature protection (T3)

Vitocal 100-SDLCLRC

What is going on

Compressor frequency is limited when the condenser coil temperature gets high.

Likely causes

  • Condenser coil temperature T3 too high

Check in this order

  1. If T3 is between 131°F and 140°F (55°C to 60°C), the compressor drops to the lower level until F1 and then runs at F1.
  2. If T3 falls below 129.2°F (54°C), the compressor holds the current frequency.
  3. If T3 is below 125.6°F (52°C), the frequency limit is removed and the previous frequency resumes.
  4. If T3 is above 140°F (60°C) for 5 seconds, the compressor stops until T3 falls below 125.6°F (52°C).

Applies to: DLCLRC

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-S DLCLRC service instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.