Condensate drain and p-trap
What is going on
The unit has an integrated p-trap. A vent is only needed where a double p-trap can form.
Likely causes
- Unlevel drain piping that lets standing water form a second p-trap, causing an air lock and no drainage
Check in this order
- Provide a condensate drain connection; add a condensate pump if needed.
- Install a vent only downstream of the unit p-trap, and only if a double p-trap condition is possible.
- Never place a vent between the unit and its p-trap.
- Install extra tees near the unit for drain cleaner access and cap or plug all extra openings.
- Never tie the condensate drain into the discharge line of a well water system.
Applies to: All Vitocal 100-WA units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.