Viessmann · Heat pump troubleshooting

Condensate drain and p-trap

Vitocal 100-WA

What is going on

The unit has an integrated p-trap. A vent is only needed where a double p-trap can form.

Likely causes

  • Unlevel drain piping that lets standing water form a second p-trap, causing an air lock and no drainage

Check in this order

  1. Provide a condensate drain connection; add a condensate pump if needed.
  2. Install a vent only downstream of the unit p-trap, and only if a double p-trap condition is possible.
  3. Never place a vent between the unit and its p-trap.
  4. Install extra tees near the unit for drain cleaner access and cap or plug all extra openings.
  5. Never tie the condensate drain into the discharge line of a well water system.

Applies to: All Vitocal 100-WA units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.