Condensate drain and double p-trap
What is going on
The unit has an integrated p-trap. A vent is only needed when a double p-trap condition exists, usually from unlevel drain piping that lets standing water form a second trap. Two or more traps cause an air lock and the unit will not drain. A vent must go downstream of the unit p-trap, never between the unit and its trap.
Likely causes
- Unlevel condensate drain piping creating a second p-trap
- Standing water in the drain line forming an air lock
Check in this order
- Make a condensate drain connection; add a condensate pump if the drain is above a suitable outlet.
- Level the drain piping so no standing water can form a second trap.
- Install a vent only if a double p-trap condition is possible, and place it downstream of the unit p-trap.
- Do not put a vent between the unit and its p-trap.
- Install extra tees near the unit for pouring drain cleaner, and cap or plug all unused openings.
- Do not run the condensate drain into the discharge line of a well water system.
Applies to: Vitocal 100-WA, all models
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA installation, service and operating instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.