Condensate drain and double p-trap

Vitocal 100-WA

What is going on

The unit has an integrated p-trap. A vent is only needed when a double p-trap condition exists, usually from unlevel drain piping that lets standing water form a second trap. Two or more traps cause an air lock and the unit will not drain. A vent must go downstream of the unit p-trap, never between the unit and its trap.

Likely causes

  • Unlevel condensate drain piping creating a second p-trap
  • Standing water in the drain line forming an air lock

Check in this order

  1. Make a condensate drain connection; add a condensate pump if the drain is above a suitable outlet.
  2. Level the drain piping so no standing water can form a second trap.
  3. Install a vent only if a double p-trap condition is possible, and place it downstream of the unit p-trap.
  4. Do not put a vent between the unit and its p-trap.
  5. Install extra tees near the unit for pouring drain cleaner, and cap or plug all unused openings.
  6. Do not run the condensate drain into the discharge line of a well water system.

Applies to: Vitocal 100-WA, all models

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA installation, service and operating instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.