Viessmann · Heat pump troubleshooting
Compressor winding resistance check
What is going on
Checks the compressor windings for balance when a compressor or IPM fault is suspected.
Check in this order
- Disconnect the compressor.
- Measure resistance between U-V, V-W and U-W.
- All three values should be equal.
- If they are not equal, the compressor is faulty and must be replaced.
Applies to: Compressor, PC00 fault
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFSHC Service Manual, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.