Viessmann · Heat pump troubleshooting

Compressor temperature protection (cooling)

Vitocal 100-S

What is going on

In cooling, the compressor frequency is limited based on condenser temperature T3 and evaporator temperature. Actions are Off, Decrease, Hold and Resume. When T3 is above the setting the compressor stops. When the evaporator temperature is below the setting the compressor stops.

Likely causes

  • Condenser temperature above setting
  • Evaporator temperature below setting

Check in this order

  1. Check condenser temperature T3 with the point check function (press 05).
  2. Check evaporator temperature T2 with the point check function (press 04).

Applies to: DLCURA outdoor unit in cooling mode

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCURA Service Manual, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.