Viessmann · Heat pump troubleshooting

Compressor protection trips

Vitocal 100-S

What is going on

Protection functions that stop the compressor or unit. No code is listed on these pages for most of them.

Likely causes

  • Compressor discharge temperature above 239°F (115°C) for 5 s
  • Compressor high temperature cutout open
  • Current above the set value
  • Inverter module fault on current, voltage or temperature
  • Zero crossing signal outside 6 to 13 ms for 240 s

Check in this order

  1. Check that the unit restarts after the cutout closes or the fault clears.
  2. Wait for the 3 min restart delay before retesting.
  3. For an inverter fault, the matching code shows on the indoor unit display.

Applies to: DLCSRB outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCSRB Service Manual, p. 18-19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.