Viessmann · Heat pump troubleshooting

Compressor discharge temperature protection (T5)

Vitocal 100-SDLCLRC

What is going on

Running frequency is limited when the compressor discharge temperature rises.

Likely causes

  • Discharge temperature rises above the protection limits

Check in this order

  1. If T5 is above 239°F (115°C) for 5 seconds, the compressor stops and restarts only after T5 falls below 194°F (90°C).
  2. If T5 is between 221°F and 239°F (105°C to 115°C), the frequency drops to a lower level every 2 minutes.
  3. If T5 is between 221°F and 230°F (105°C to 110°C), the frequency holds at the current level.
  4. If T5 is below 221°F (105°C), there is no frequency limit.

Applies to: DLCLRC compressor

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-S DLCLRC service instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.