Viessmann · Heat pump troubleshooting

Compressor check

Vitocal 100-SDLCSRB

What is going on

Checks the compressor windings for balance.

Check in this order

  1. Disconnect the compressor.
  2. Measure the resistance between U-V, V-W and U-W.
  3. All three values should be equal. If they are not, the compressor is faulty and must be replaced.

Applies to: DLCSRB outdoor units, sizes 06 to 36

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocal 100-S DLCSRB service manual, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.