Viessmann · Heat pump troubleshooting
Communication signal voltage interpretation (S line, port 2 to port 3)
What is going on
Interprets the DC voltage on the communication line between the outdoor unit ports 2 and 3, or S and N, or L2 and S.
Check in this order
- Measure with the red probe on port 2 (or S or L2) and the black probe on port 3 (or N or S).
- Normal running voltage alternates between positive and negative values.
- Outdoor unit fault voltage is always positive.
- Indoor unit fault voltage stays at one fixed value.
- To check a reactor, measure its resistance with no capacitor connected. A normal reactor reads close to zero ohms. Otherwise the reactor is faulty.
- Readings in the reference images are for guidance only. Actual values can vary.
Applies to: DLCLRC outdoor unit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLCLRC Service Manual, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.