Viessmann · Heat pump troubleshooting

Communication signal voltage interpretation (S line, port 2 to port 3)

Vitocal 100-S

What is going on

Interprets the DC voltage on the communication line between the outdoor unit ports 2 and 3, or S and N, or L2 and S.

Check in this order

  1. Measure with the red probe on port 2 (or S or L2) and the black probe on port 3 (or N or S).
  2. Normal running voltage alternates between positive and negative values.
  3. Outdoor unit fault voltage is always positive.
  4. Indoor unit fault voltage stays at one fixed value.
  5. To check a reactor, measure its resistance with no capacitor connected. A normal reactor reads close to zero ohms. Otherwise the reactor is faulty.
  6. Readings in the reference images are for guidance only. Actual values can vary.

Applies to: DLCLRC outdoor unit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLCLRC Service Manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.