Viessmann · Heat pump troubleshooting
Communication line and reactor checks (remarks)
What is going on
Test notes for the communication signal and the reactor used with EL01 diagnosis.
Likely causes
- Reactor shorted to ground
- Reactor open or shorted
Check in this order
- Use a multimeter to measure DC voltage between the 2 port (or S or L2) and the 3 port (or N or S). Red probe on the 2 port (or S or L2), black on the 3 port (or N or S).
- A running unit shows a voltage that alternates between positive and negative values.
- If the outdoor unit is faulty, the voltage stays in a narrow positive range.
- If the indoor unit is faulty, the voltage stays fixed.
- Measure the reactor resistance with the reactor disconnected from the capacitor. Normal is about zero ohms. If not, the reactor is faulty. Check that it is not shorted to ground.
Applies to: DLFSHC outdoor unit, EL01 diagnosis
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.