Viessmann · Heat pump troubleshooting
Closed loop water quality and antifreeze requirements
What is going on
Requirements for fill and top-up water and for antifreeze in closed loop ground systems.
Likely causes
- Antifreeze below the minimum level lets the system freeze and damage the unit, and this is not covered by warranty.
- Sulphur in feed water, high hardness or wrong pH can cause build-up and problems.
Check in this order
- Keep at least 25% propylene glycol in the unit and ground loop at all times.
- Do not exceed 35% antifreeze. Above 35% reduces performance, so account for it in equipment selection.
- Use only antifreeze made for water source heat pumps. Do not use automotive silicate based antifreeze.
- Check that feed water has no sulphur and that pH is between 7 and 9 after some run time. Treat the water if it is not.
- Keep total hardness of fill and top-up water below 350 ppm. Treat hard water where needed.
- Check for a backflow preventer in the automatic feed when using antifreeze.
- Check that expansion tanks, radiation and other components are compatible with the glycol mix.
- Check the total system often when it is filled with antifreeze.
- Tell the owner the system contains a glycol mix and give them the antifreeze Safety Data Sheet.
Applies to: Vitocal 100-WA closed loop systems
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA installation, service and operating instructions, p. 75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.