Viessmann · Heat pump troubleshooting

Closed loop water quality and antifreeze requirements

Vitocal 100-WA

What is going on

Requirements for fill and top-up water and for antifreeze in closed loop ground systems.

Likely causes

  • Antifreeze below the minimum level lets the system freeze and damage the unit, and this is not covered by warranty.
  • Sulphur in feed water, high hardness or wrong pH can cause build-up and problems.

Check in this order

  1. Keep at least 25% propylene glycol in the unit and ground loop at all times.
  2. Do not exceed 35% antifreeze. Above 35% reduces performance, so account for it in equipment selection.
  3. Use only antifreeze made for water source heat pumps. Do not use automotive silicate based antifreeze.
  4. Check that feed water has no sulphur and that pH is between 7 and 9 after some run time. Treat the water if it is not.
  5. Keep total hardness of fill and top-up water below 350 ppm. Treat hard water where needed.
  6. Check for a backflow preventer in the automatic feed when using antifreeze.
  7. Check that expansion tanks, radiation and other components are compatible with the glycol mix.
  8. Check the total system often when it is filled with antifreeze.
  9. Tell the owner the system contains a glycol mix and give them the antifreeze Safety Data Sheet.

Applies to: Vitocal 100-WA closed loop systems

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA installation, service and operating instructions, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.