Closed loop water quality and antifreeze limits
What is going on
Treat feed water where mineral content or hardness is high. Keep total hardness of fill and top-up water under 350 ppm and avoid sulphur-containing feed water. Check pH after running; it should be 7 to 9. Use only antifreeze made for water source heat pumps, never automotive silicate antifreeze. Keep antifreeze at or below 35%; above that performance drops. Provide the owner with the SDS for the antifreeze used.
Likely causes
- Hardness above 350 ppm
- pH outside 7 to 9
- Silicate-based automotive antifreeze
- Antifreeze above 35%
Check in this order
- Test fill water for hardness and sulphur; treat if needed.
- Check pH after operation; correct it if outside 7-9.
- Use only heat pump rated antifreeze.
- Keep glycol at or below 35%.
- Give the owner the antifreeze SDS and note the system is glycol filled.
Applies to: Closed loop systems
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA technical data manual, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.