Viessmann · Heat pump troubleshooting

Closed loop piping and antifreeze rules

Vitocal 100-WA

What is going on

Do not use PVC or CPVC on ground loop connections; these may only be used as condensate lines. The loop and unit must hold at least 25% propylene glycol at all times, or the unit can freeze and damage will not be covered. Purge each branch of the loop at a minimum of 2 ft/s, and use the purge ports for antifreeze charging.

Likely causes

  • Antifreeze below 25% propylene glycol
  • PVC or CPVC used on loop piping

Check in this order

  1. Use only non-PVC/CPVC pipe on the loop connections.
  2. Verify 25% minimum propylene glycol in the unit and loop.
  3. Purge every loop branch at 2 ft/s minimum.
  4. Install isolation valves and purge ports for purging and antifreeze charging.

Applies to: Closed loop systems

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA technical data manual, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.