Viessmann · Heat pump troubleshooting

Closed loop (ground loop) piping and antifreeze

Vitocal 100-WA

What is going on

Ground loops must always hold a minimum of 25% propylene glycol. Failure freezes the system and damages the unit, and that damage is not covered by warranty.

Likely causes

  • Antifreeze below 25% propylene glycol, causing freeze damage
  • Insufficient loop velocity leaving air or debris in branches

Check in this order

  1. Do not use PVC or CPVC piping on any ground loop connection; PVC or CPVC may only be used for condensate lines.
  2. Size the loop pump to the project-specific loop design; residential systems typically need one pump per unit.
  3. Provide suitable access for purging the outside loop and isolation valves for purging the inside plumbing.
  4. Purge the loop so every branch reaches a minimum velocity of 2 feet per second.
  5. Use the purge ports for anti-freeze charging.
  6. Keep a minimum of 25% propylene glycol in the unit and ground loop at all times.

Applies to: Vitocal 100-WA closed loop systems

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-WA installation, service and operating instructions, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.