Viessmann · Heat pump troubleshooting
Closed loop (ground loop) piping and antifreeze
What is going on
Ground loops must always hold a minimum of 25% propylene glycol. Failure freezes the system and damages the unit, and that damage is not covered by warranty.
Likely causes
- Antifreeze below 25% propylene glycol, causing freeze damage
- Insufficient loop velocity leaving air or debris in branches
Check in this order
- Do not use PVC or CPVC piping on any ground loop connection; PVC or CPVC may only be used for condensate lines.
- Size the loop pump to the project-specific loop design; residential systems typically need one pump per unit.
- Provide suitable access for purging the outside loop and isolation valves for purging the inside plumbing.
- Purge the loop so every branch reaches a minimum velocity of 2 feet per second.
- Use the purge ports for anti-freeze charging.
- Keep a minimum of 25% propylene glycol in the unit and ground loop at all times.
Applies to: Vitocal 100-WA closed loop systems
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-WA installation, service and operating instructions, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.