Viessmann · Heat pump troubleshooting
Check the indoor unit fuse
What is going on
The indoor unit fuse is on the indoor unit main board. Fuse type T 5.0 A H, 250 V~. Battery type CR2032. Replacing with an incorrect fuse increases fire risk. Removing the fuse does not disconnect the load circuit.
Check in this order
- Switch off the power supply.
- Check the fuse and replace it if necessary with a T 5.0 A H, 250 V~ fuse.
- Disconnect the load circuit as well when working on the unit.
- Wait 30 seconds for capacitors to discharge before any work.
Applies to: Indoor unit main board
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 87. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.