Viessmann · Heat pump troubleshooting

Check temperature sensors

Vitocal 100-AW AM2V

What is going on

All sensors connect to the indoor unit and are NTC 10 kΩ. They connect to a low-voltage printed circuit board. Sensors: DHW tank temperature, system supply water temperature, room temperature (room sensors) and outdoor temperature.

Check in this order

  1. Measure sensor resistance and compare it with the temperature vs. resistance table in the manual.
  2. Replace the sensor if its resistance is out of range.

Applies to: Indoor unit sensors

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.