ICP · Furnace troubleshooting

Reading and retrieving status codes

What is going on

Status LED: heartbeat (bright-dim) = normal; code = short flashes (first digit) then long flashes (second digit). Up to 7 codes are stored and survive power loss.

Check in this order

  1. Look through the blower door sight glass at the amber LED before removing the door.
  2. With no thermostat call and blower off-delay finished, leave 115 V on, remove the blower door, turn SW1-1 ON and hold the door switch closed.
  3. The LED flashes up to 7 stored codes in order; the 8th is a heartbeat.
  4. Turn SW1-1 OFF; a heartbeat means normal; replace door.
  5. Codes clear after 72 hours, or manually SW1-1 ON and jumper R, W/W1 and Y/Y2 together until heartbeat, then SW1-1 OFF.
  6. Note the flowchart version says to disconnect R and reset power before SW1-1 ON.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Retrieving Stored Fault Codes / Figure 16, p.24, p.33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.