ICP · Furnace troubleshooting
Component self-test
What is going on
Component self-test on the ICP F9MAE and G9MAE modulating variable-speed furnaces. Runs the inducer, checks gas valve communication, heats the igniter and runs the blower. Use it to find a dead part without a call for heat. Line voltage is live with the door switch held closed, so be careful. Sizes 060, 080, 100, 120 kBtu/h.
Likely causes
- Furnace dead or not completing a start sequence and you want to isolate the part
- Suspect inducer, igniter or blower but no code explains it
- Checking a repair before putting the door back
- Heartbeat LED but unclear which component failed
Check in this order
- Warning: door switch held closed exposes live 115 V parts, keep hands and tools clear
- Remove the blower door and the wire from R on the control
- Turn SW1-6 ON and close the door switch
- Inducer runs at medium speed, control checks gas valve communication, after 15 s the igniter heats for 15 s, then blower runs at mid airflow for 15 s
- Afterwards heartbeat, 2+5, 3+5, 4+1 or 4+2 may flash, see those codes
- Turn SW1-6 OFF and back ON to repeat
- When done turn SW1-6 OFF, reconnect R and replace door, and have a licensed tech handle any live-voltage work you are not trained for
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Component Self-Test, p.24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.