ICP · Furnace troubleshooting
No heat - control does not respond to thermostat
What is going on
So your ICP F9MAE or G9MAE shows the LED heartbeat, there are no stored fault codes, but the furnace just ignores the thermostat. That's actually a helpful clue, because the control is alive and not seeing any problem, it just isn't getting or accepting the call. Start by finding out whether 24 V is actually arriving at the board. If it is, you can test the control by calling for heat right at the board. Some thermostats, especially power-stealing ones, just don't play well with this control.
Likely causes
- Thermostat or thermostat cable fault
- Thermostat not compatible with the control
- Failed furnace control
Check in this order
- Check for 24 V at W/W1, W2, Y1, Y/Y2 or G on the furnace control during a call, with the meter on AC volts and the stat calling
- No 24 V: check the thermostat and cable, look for a broken conductor, a loose terminal or a wrong wire
- 24 V present but no response: disconnect all thermostat wires and call for heat directly at the board by connecting R to W/W1 etc. with a short test lead
- If it works at the board, the thermostat is not compatible: add a ballast resistor, connect Com24V to the thermostat, or replace the thermostat
- If it still does not respond at the board, replace the furnace control
- Remove the test lead when finished and restore the thermostat wiring
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.