ICP · Furnace troubleshooting

Check inlet gas pressure

What is going on

Low inlet gas pressure on the ICP F9MAE and G9MAE keeps you from setting the right input and causes ignition and pressure switch faults. Check it with a manometer at the valve inlet tap while the furnace is at maximum fire. Never purge gas into the combustion chamber and never use a flame to look for leaks. Gas work belongs to a licensed technician.

Likely causes

  • Undersized or partly restricted gas line
  • Regulator at the meter or line not delivering enough at full fire
  • Other gas appliances dropping the pressure when running
  • Wrong manifold setting from a previous service call

Check in this order

  1. Warning: never purge gas into the combustion chamber, leak test with soap solution only
  2. Gas off, remove the 1/8 in. NPT plug at the gas valve inlet tap and connect a manometer
  3. Power on, gas on, call for maximum heat by connecting R to W/W1 and W2 at the control
  4. With burners lit, inlet pressure must be between 4.5 and 13.6 in. w.c. (natural gas)
  5. If it drops when other gas appliances run, the line or regulator is undersized
  6. Remove the test lead, gas off, remove manometer, refit plug with a little pipe dope and leak test
  7. Do not set maximum heat manifold pressure below 3.2 in. w.c. on natural gas, change orifices instead

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Check Inlet Gas Pressure / Adjust Manifold Pressure. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.