KeepRite · Furnace troubleshooting

No heat, control ignores the thermostat - KeepRite (F/G)9MXT

What is going on

The status light on the KeepRite (F/G)9MXT is pulsing a heartbeat, but the furnace won't respond to W, Y or G. A heartbeat tells you the control has power and is running its program. So the issue is between the thermostat and the board, or the board itself.

Likely causes

  • Thermostat or thermostat cable fault
  • Thermostat not compatible with the control
  • Failed furnace control

Check in this order

  1. Confirm the green light is pulsing (heartbeat), because if it is not, the LED codes come first
  2. With a call, measure 24 V at W, Y1, Y/Y2 or G on the board, this shows whether the call arrives
  3. No 24 V: check the thermostat and cable
  4. 24 V present but no response: replace the control
  5. If calling at the board with a test lead works but the thermostat does not, the thermostat is not compatible: add a ballast resistor, connect the C terminal, or change the thermostat
  6. Turn power off before moving wires, and restore all wiring afterward

Applies to: KeepRite (F/G)9MXT furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Fig. 16 flow chart, p.24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.