No heat, control ignores the thermostat - KeepRite (F/G)9MXE
What is going on
KeepRite (F/G)9MXE. Green status light pulses heartbeat, so the board is alive. Furnace ignores W, Y or G. Control is fine on its own, so the call is not getting in. Find the 24 V.
Likely causes
- Thermostat or thermostat cable fault
- Thermostat not compatible with the control
- Failed furnace control
Check in this order
- Confirm the green light is pulsing (heartbeat), if not, use the LED codes first
- With a call, measure 24 V at W, Y1, Y/Y2 or G on the board
- No 24 V: check the thermostat and cable for breaks and loose terminals
- 24 V present but no response: replace the control
- If calling for heat directly at the board with a test lead works but the thermostat does not, the thermostat is not compatible: add a ballast resistor, connect the C terminal, or change the thermostat
- Remove the test lead and restore wiring when done
- Power off before changing any wiring
Applies to: KeepRite (F/G)9MXE furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 flow chart, p.24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.