Pump noisy at start-up

What is going on

If the circulator is loud for the first few seconds of a call and then settles down, there's almost always air trapped in the hot water loop. It's common on a new install or after anything on the system has been opened up, and it can keep coming back if the loop is slowly losing pressure or a fitting is pulling air in. A pump that runs dry for any length of time wears out early, so it's worth sorting out properly.

Likely causes

  • Air in the hot water loop
  • Loop pressure too low from a small leak or a poor fill
  • Manual air vents or purge points never fully opened after the install
  • Worn pump bearings, if it stays loud after a good purge

Check in this order

  1. Purge the air from the hot water loop.
  2. Check the loop pressure on the gauge and top it up to the figure in the install manual if it's low.
  3. Open the manual air vents on the coil and at the high points in the piping and bleed until the water runs steady with no spitting.
  4. Run a few heat cycles and listen again.
  5. If it's still noisy after a proper purge, look for a leak or a worn pump before replacing anything else.

Applies to: Rinnai Canadian hydronic air handler (CAH050E) with a Rinnai water heater/boiler

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai Canadian Air Handler Installation and Operation Manual (600000023), Troubleshooting, p.40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.