Rinnai · Air handler troubleshooting

Insufficient or no heat

What is going on

The air handler runs but delivers little or no heat from the hydronic coil.

Likely causes

  • Dirty air filter
  • Clogged hydronic coil
  • Air trapped in the heating loop
  • Rinnai heater not running or water temperature too low
  • Dirty inlet water filter on the Rinnai heater
  • Restriction or partly closed valve in the heating loop

Check in this order

  1. Check the air filter and replace it if dirty.
  2. Make sure the hydronic coil is not clogged.
  3. Check for air in the heating loop and purge the loop if needed.
  4. Confirm the Rinnai heater is running and check the supply water temperature.
  5. Clean the inlet water filter on the Rinnai heater.
  6. Check the heating loop for restrictions and make sure all valves are fully open and working.

Applies to: Rinnai Canadian hydronic air handler (CAH050E) with a Rinnai water heater/boiler

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai Canadian Air Handler Installation and Operation Manual (600000023), Troubleshooting, p.40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.