Rinnai · Air handler troubleshooting
Heat comes out in fan-only mode
What is going on
The thermostat is on fan only and warm air still comes out of the registers. That's hot water working its way through the coil when nothing is calling for heat. On a hydronic air handler the usual reason is a check valve in the heating circuit that's missing, installed backwards, or not sealing.
Likely causes
- Check valve in the heating circuit missing or stuck open
- Check valve installed backwards
- Debris under the valve seat keeping it from closing
Check in this order
- Make sure the check valve in the heating circuit is installed and is not stuck open.
- Confirm the arrow on the valve body points the same way the water flows.
- With the system idle, feel the supply pipe at the coil. If it stays hot with no call for heat, the valve is leaking by.
- Flush or replace the check valve. Isolate and let the loop cool first, the water can scald.
- Refill, purge the air, and test again in fan-only mode.
Applies to: Rinnai Canadian hydronic air handler (CAH050E) with a Rinnai water heater/boiler
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai Canadian Air Handler Installation and Operation Manual (600000023), Troubleshooting, p.40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.