Rinnai · Air handler troubleshooting

Circulator pump does not run

What is going on

On the Rinnai Canadian hydronic air handler (CAH050E), the external pump on the hydronic loop is supposed to start whenever there is a call for heat. If it just sits there, the loop gets no hot water and the house stays cold even though the water heater or boiler is working fine. The two things I would look at first are power and a seized pump.

Likely causes

  • No 120 V power reaching the pump
  • Pump seized up from hard water scale after sitting idle

Check in this order

  1. Check that 120 V power is actually reaching the pump. Shut the power off before touching terminals, then use a meter once you are back on a live circuit and checking correctly.
  2. Hard water can seize the pump. If it will not turn, it likely needs replacing.
  3. To keep it from happening again, leave the recirculation setting active in the Pump menu so the pump runs periodically and does not seize.
  4. After any fix, call for heat and confirm the pump starts and the loop warms up

Applies to: Rinnai Canadian hydronic air handler (CAH050E) with a Rinnai water heater/boiler

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai Canadian Air Handler Installation and Operation Manual (600000023), Troubleshooting, p.40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.