York · Furnace
LAST ERROR button Read or clear the stored fault codes
What the display is showing
The board keeps up to five fault codes, newest first, even after power loss. Solid-LED errors are not stored. Retrieval only works when no thermostat signal is active.
Applies to: York IFC boards with LAST ERROR button
What to do
- End any heating, cooling or continuous-fan call first.
- Press and release LAST ERROR (more than 1/5 s, under 5 s). The LED flashes the stored codes starting with the most recent, with a 2 second pause between them.
- TM9V: after the codes it returns to slow green flash after a 5 second pause. Press again to repeat.
- Two green flashes = nothing stored.
- To clear, hold the button 5 seconds or more; three green flashes confirm.
Settings for these units
Clearance to combustibles · York TM9V
| Side of furnace | Upflow | Downflow | Horizontal |
|---|---|---|---|
| Top / vent / rear / side / front | ? | ? | ? |
| Combustible floor | Yes | Yes (special sub-base only) | Yes |
| Closet | Yes | Yes | Yes |
| Line contact | No | No | Yes |
Leave about 24 in. at the front and 18 in. at the side for service.
Approved for alcove and attic installs.
Filter size by return location · York TM9V
| Airflow | Cabinet | Side return filter | Bottom return filter |
|---|---|---|---|
| 1000 CFM | A | 16 x 25 in. | 14 x 25 in. |
| 1200 CFM | B | 16 x 25 in. | 16 x 25 in. |
| 1600 CFM | C | 16 x 25 in. | 20 x 25 in. |
| 2000 CFM | C | (2) 16 x 25 in. | 20 x 25 in. |
| 2000 CFM | D | (2) 16 x 25 in. | 22 x 25 in. |
Sizes assume high velocity filters (600 FPM); throwaway filters must stay at or below 300 FPM.
Filters go outside the cabinet - never inside the furnace.
Models that show this code
7 models in York UTEC IFC furnaces, York White-Rodgers IFC furnaces, York TM9V
Other codes on the same units
- 12 red flashes Hot surface igniter open / igniter failure
- 13 red flashes High-fire pressure switch open
- Amber heartbeat Normal - call for heat, first stage on
- Green heartbeat Idle - no call for heat
- LED steady off Board LED dark - no power to control
- Rapid amber flash Weak flame signal
- Rapid red flash Twinning error or wrong 24 V phasing
- Slow amber flash Normal - call for heat
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: York service letter ST-028-07 White Rodgers/Emerson IFC boards, Fault Code Sheet, p.5-7; York service tip ST-045-09 UTEC IFC boards, Fault Code Sheet; York TM9V installation manual 1083294-UIM-A-0114, Fault Code Storage and Retrieval, p.42. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.