York · Furnace
12 red flashes Hot surface igniter open / igniter failure
What the control is telling you
The board detects an open or failed hot surface igniter circuit.
Applies to: York/JCI residential gas furnaces: York UTEC IFC furnaces, York White-Rodgers IFC furnaces
Likely causes
- Burnt or cracked igniter
- Broken igniter wiring or plug
- Board igniter relay
Test and repair steps
- Check igniter resistance with power off; open circuit means replace.
- Check the igniter plug and wires.
- Check for 115 V to the igniter at warm-up; if missing, replace the board.
- To read stored codes with no thermostat call active, tap the LAST ERROR button briefly (under 5 s); up to five codes play back newest first. Two green flashes = memory empty. Hold the button 5 s or more to clear (three green flashes confirm).
Settings for these units
- Clearance to combustibles · York TM9V
- Filter size by return location · York TM9V
Other codes on the same units
- 7 red flashes Ignition failure lockout (retries)
- 8 red flashes Flame lost repeatedly (recycles)
- 9 red flashes Polarity reversed or bad ground
- 10 red flashes Gas valve powered with no heat call
- 11 red flashes Limit open 5-15 minutes - blower failure
- Amber heartbeat Normal - call for heat, first stage on
- Green heartbeat Idle - no call for heat
- LAST ERROR button Read or clear the stored fault codes
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: York All JCI single-two-stage furnaces with UTEC IFC board codes ST-045-09.pdf - section Fault Code LED Flashes; York JCI single-two-stage furnaces with White-Rodgers-Emerson IFC (older installed base) codes ST-028-07.pdf - section Fault Code Sheets. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.