York · Furnace
4 red flashes Main limit switch open
What the control is telling you
The high limit has opened. The board runs the blower and inducer. If the limit opens 5 times in one call the furnace goes into a 1-hour soft lockout. If it stays open 5 minutes the code changes to 11 red; after 15 minutes to 5 red.
Applies to: York/JCI residential gas furnaces: York UTEC IFC furnaces, York White-Rodgers IFC furnaces, York TM9V
Likely causes
- Dirty filter
- Undersized or restricted ductwork / closed registers
- Blower speed set too low
- Overfiring (high gas pressure)
- Failed blower motor
- Loose limit wiring
Test and repair steps
- Replace or clean the filter and open all registers.
- Measure temperature rise and compare with the rating plate range.
- Check blower speed/airflow jumper settings for the furnace size.
- Check manifold pressure and input rate.
- Check limit switch wiring; confirm the blower actually runs.
- To read stored codes with no thermostat call active, tap the LAST ERROR button briefly (under 5 s); up to five codes play back newest first. Two green flashes = memory empty. Hold the button 5 s or more to clear (three green flashes confirm).
Settings for these units
Clearance to combustibles · York TM9V
| Side of furnace | Upflow | Downflow | Horizontal |
|---|---|---|---|
| Top / vent / rear / side / front | ? | ? | ? |
| Combustible floor | Yes | Yes (special sub-base only) | Yes |
| Closet | Yes | Yes | Yes |
| Line contact | No | No | Yes |
Leave about 24 in. at the front and 18 in. at the side for service.
Approved for alcove and attic installs.
Filter size by return location · York TM9V
| Airflow | Cabinet | Side return filter | Bottom return filter |
|---|---|---|---|
| 1000 CFM | A | 16 x 25 in. | 14 x 25 in. |
| 1200 CFM | B | 16 x 25 in. | 16 x 25 in. |
| 1600 CFM | C | 16 x 25 in. | 20 x 25 in. |
| 2000 CFM | C | (2) 16 x 25 in. | 20 x 25 in. |
| 2000 CFM | D | (2) 16 x 25 in. | 22 x 25 in. |
Sizes assume high velocity filters (600 FPM); throwaway filters must stay at or below 300 FPM.
Filters go outside the cabinet - never inside the furnace.
Models that show this code
7 models in York UTEC IFC furnaces, York White-Rodgers IFC furnaces, York TM9V
Other codes on the same units
- 3 double red flashes Second-stage pressure switch not closing
- 3 green flashes Fault memory cleared
- 3 red flashes Pressure switch open when it should be closed
- 4 amber flashes Cooling call (Y) without fan call (G)
- 5 red flashes Rollout switch open / limit circuit open over 15 min
- 6 red flashes Pressure switch cycling lockout
- 7 red flashes Ignition failure lockout (retries)
- 8 red flashes Flame lost repeatedly (recycles)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: York All JCI single-two-stage furnaces with UTEC IFC board codes ST-045-09.pdf - section Fault Code LED Flashes; York JCI single-two-stage furnaces with White-Rodgers-Emerson IFC (older installed base) codes ST-028-07.pdf - section Fault Code Sheets; York TM9V - -M9V 96% two-stage variable speed installation 1083294-UIM-A-0114.pdf - section Furnace Control Diagnostics. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.