York · Furnace
3 red flashes Pressure switch open when it should be closed
What the control is telling you
The (first-stage) pressure switch does not close after the inducer starts.
Applies to: York/JCI residential gas furnaces: York UTEC IFC furnaces, York White-Rodgers IFC furnaces, York TM9V
Likely causes
- Inducer motor failed or weak
- Blocked vent or intake pipe / termination
- Cracked, kinked or water-filled pressure switch hose
- Blocked condensate drain (condensing models)
- Loose or disconnected wires
- Faulty pressure switch
Test and repair steps
- Confirm the inducer starts and runs at speed.
- Inspect vent and intake pipes and terminations for blockage, ice, nests.
- Check the hose from the switch to the port - no cracks, kinks or water.
- Clear the condensate trap and drain on condensing models.
- Check switch wiring, then test the switch with a manometer against its rating; replace if bad.
- Warning: Never bypass or adjust a pressure switch to make the furnace run.
- To read stored codes with no thermostat call active, tap the LAST ERROR button briefly (under 5 s); up to five codes play back newest first. Two green flashes = memory empty. Hold the button 5 s or more to clear (three green flashes confirm).
Settings for these units
Clearance to combustibles · York TM9V
| Side of furnace | Upflow | Downflow | Horizontal |
|---|---|---|---|
| Top / vent / rear / side / front | ? | ? | ? |
| Combustible floor | Yes | Yes (special sub-base only) | Yes |
| Closet | Yes | Yes | Yes |
| Line contact | No | No | Yes |
Leave about 24 in. at the front and 18 in. at the side for service.
Approved for alcove and attic installs.
Filter size by return location · York TM9V
| Airflow | Cabinet | Side return filter | Bottom return filter |
|---|---|---|---|
| 1000 CFM | A | 16 x 25 in. | 14 x 25 in. |
| 1200 CFM | B | 16 x 25 in. | 16 x 25 in. |
| 1600 CFM | C | 16 x 25 in. | 20 x 25 in. |
| 2000 CFM | C | (2) 16 x 25 in. | 20 x 25 in. |
| 2000 CFM | D | (2) 16 x 25 in. | 22 x 25 in. |
Sizes assume high velocity filters (600 FPM); throwaway filters must stay at or below 300 FPM.
Filters go outside the cabinet - never inside the furnace.
Models that show this code
7 models in York UTEC IFC furnaces, York White-Rodgers IFC furnaces, York TM9V
Other codes on the same units
- 2 red flashes Pressure switch closed when it should be open
- 3 amber flashes W2 call without W1
- 3 double red flashes Second-stage pressure switch not closing
- 3 green flashes Fault memory cleared
- 4 amber flashes Cooling call (Y) without fan call (G)
- 4 red flashes Main limit switch open
- 5 red flashes Rollout switch open / limit circuit open over 15 min
- 6 red flashes Pressure switch cycling lockout
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: York All JCI single-two-stage furnaces with UTEC IFC board codes ST-045-09.pdf - section Fault Code LED Flashes; York JCI single-two-stage furnaces with White-Rodgers-Emerson IFC (older installed base) codes ST-028-07.pdf - section Fault Code Sheets; York TM9V - -M9V 96% two-stage variable speed installation 1083294-UIM-A-0114.pdf - section Furnace Control Diagnostics. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.