York · Furnace

1 red flash Flame detected with gas valve off

Critical severity York UTEC IFC furnacesYork White-Rodgers IFC furnacesYork TM9V

What the control is telling you

Flame is seen when there should be none. The board runs the inducer and the main blower to clear the heat.

Applies to: York/JCI residential gas furnaces: York UTEC IFC furnaces, York White-Rodgers IFC furnaces, York TM9V

Likely causes

  • Gas valve leaking through or closing slowly
  • Flame sensor circuit fault

Test and repair steps

  1. Warning: Shut off gas at the manual valve if flame remains after the call ends.
  2. Watch the burners after the thermostat is satisfied - any flame means the valve is passing gas.
  3. Replace a leaking or slow-closing gas valve.
  4. Check the flame sensor wiring for shorts.
  5. To read stored codes with no thermostat call active, tap the LAST ERROR button briefly (under 5 s); up to five codes play back newest first. Two green flashes = memory empty. Hold the button 5 s or more to clear (three green flashes confirm).

Settings for these units

Clearance to combustibles · York TM9V

Side of furnaceUpflowDownflowHorizontal
Top / vent / rear / side / front???
Combustible floorYesYes (special sub-base only)Yes
ClosetYesYesYes
Line contactNoNoYes

Leave about 24 in. at the front and 18 in. at the side for service.

Approved for alcove and attic installs.

Filter size by return location · York TM9V

AirflowCabinetSide return filterBottom return filter
1000 CFMA16 x 25 in.14 x 25 in.
1200 CFMB16 x 25 in.16 x 25 in.
1600 CFMC16 x 25 in.20 x 25 in.
2000 CFMC(2) 16 x 25 in.20 x 25 in.
2000 CFMD(2) 16 x 25 in.22 x 25 in.

Sizes assume high velocity filters (600 FPM); throwaway filters must stay at or below 300 FPM.

Filters go outside the cabinet - never inside the furnace.

Models that show this code

7 models in York UTEC IFC furnaces, York White-Rodgers IFC furnaces, York TM9V

TM9V040A10TM9V060B12TM9V080B12TM9V080C16TM9V100C16TM9V100C20TM9V120D20

Other codes on the same units

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: York All JCI single-two-stage furnaces with UTEC IFC board codes ST-045-09.pdf - section Fault Code LED Flashes; York JCI single-two-stage furnaces with White-Rodgers-Emerson IFC (older installed base) codes ST-028-07.pdf - section Fault Code Sheets; York TM9V - -M9V 96% two-stage variable speed installation 1083294-UIM-A-0114.pdf - section Furnace Control Diagnostics. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.