Viessmann · Boiler
F.346 Ionization current calibration error
What the control is telling you
Burner in a fault state.
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
Likely causes
- Gas supply
- Strainer or electrode dirt
- Flue recirculation
- Condensate back-up
Test and repair steps
- Check gas supply pressure.
- Check gas valve inlet strainer.
- Check ionization electrode for contamination.
- Check flue system and remove recirculation.
- Check cable to the fan unit.
- Check for condensate back-up.
- Reset the appliance.
Models that show this code
3 models in Vitodens 200-W B2HE
Other codes on the same units
- F.299 Time and date incorrect
- F.30 Low loss header sensor short circuit
- F.342 BCU communication error
- F.345 Temperature limiter tripped, auto restart after cooling
- F.348 Gas modulation valve fault
- F.349 Air mass flow not detected correctly
- F.350 Ionization current outside permitted range (BCU)
- F.351 Ionization current outside permitted range (BCU)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.