Viessmann · Boiler

F.345 Temperature limiter tripped, auto restart after cooling

High severity Vitodens 200-W B2HE

What the control is telling you

Burner locked out; restarts on its own after cool-down.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Poor heat transfer
  • Low water
  • Expansion tank pre-charge
  • Low flow
  • 3-way valve fault
  • Scaling of DHW tank or plate exchanger

Test and repair steps

  1. Ensure adequate heat transfer.
  2. Check fill level and expansion tank pre-charge.
  3. Check flow (flow sensor and pump).
  4. Test the 3-way diverter valve in the actuator test and vent the system.
  5. If it occurs during DHW heating, check the tank or plate heat exchanger for dirt and scale.

Models that show this code

3 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-85

Other codes on the same units

  • F.29 Low loss header sensor open circuit
  • F.299 Time and date incorrect
  • F.30 Low loss header sensor short circuit
  • F.342 BCU communication error
  • F.346 Ionization current calibration error
  • F.348 Gas modulation valve fault
  • F.349 Air mass flow not detected correctly
  • F.350 Ionization current outside permitted range (BCU)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.