F.30 Low loss header sensor short circuit
What the control is telling you
Control runs without the low loss header supply sensor.
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
Likely causes
- Shorted low loss header sensor
Test and repair steps
- Check the low loss header supply temperature sensor.
- Measure sensor input on the electronics module: about 3.3 V DC with sensor unplugged.
Models that show this code
4 models in Vitodens 200-W B2HE
Other codes on the same units
- F.184 Supply temperature sensor / high limit short circuit
- F.185 Supply temperature sensor / high limit open circuit
- F.29 Low loss header sensor open circuit
- F.299 Time and date incorrect
- F.342 BCU communication error
- F.345 Temperature limiter tripped, auto restart after cooling
- F.346 Ionization current calibration error
- F.348 Gas modulation valve fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.