Viessmann · Boiler
F.343 Short circuit, common return sensor (low loss header)
What the control is telling you
Control runs without the low loss header return temperature sensor.
Applies to: Vitocrossal 200 CI2 with low loss header
Likely causes
- Short circuit in the common return sensor circuit.
- Low loss header setting in the commissioning assistant is wrong.
Test and repair steps
- Check the low loss header setting in the commissioning assistant and correct if needed.
- Check the return temperature sensor for the low loss header.
- Measure the sensor input on the electronics module. Target 3.3 V DC with sensor disconnected.
Models that show this code
21 models in Vitocrossal 200 CI2
Other codes on the same units
- F.1004 Reverse flow of flue gas in dry mode (CI2 1500/2000, partial load)
- F.1061 Faulty BCU or faulty lead from O2 probe to BCU
- F.1062 O2 controller and BCU measurements disagree
- F.344 Lead break, common return sensor (low loss header)
- F.347 Oxygen content fell below 0%: safety shutdown
- F.364 Internal system fault
- F.365 Gas fitting relay monitoring has responded
- F.371 Fan speed not reached, below minimum speed
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 64. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.