Viessmann · Boiler
F.1004 Reverse flow of flue gas in dry mode (CI2 1500/2000, partial load)
What the control is telling you
The system is in a fault state because flue gas flows in reverse during dry mode in the partial load range of the CI2 1500/2000 models.
Applies to: Vitocrossal 200 CI2 1500/2000
Likely causes
- Flue system problem on CI2 1500/2000
- Faulty burner fan in dry mode
- Flue gas damper or its connection faulty
Test and repair steps
- Check the flue system on CI2 1500/2000 and the burner fan in dry mode. Replace the fan if necessary.
- Check the flue gas damper and its connection.
Models that show this code
21 models in Vitocrossal 200 CI2
Other codes on the same units
- F.1001 Burner control unit not calibrated
- F.1002 Burner control unit not calibrated
- F.1061 Faulty BCU or faulty lead from O2 probe to BCU
- F.1062 O2 controller and BCU measurements disagree
- F.343 Short circuit, common return sensor (low loss header)
- F.344 Lead break, common return sensor (low loss header)
- F.347 Oxygen content fell below 0%: safety shutdown
- F.364 Internal system fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CI2 Service Instructions, p. 74. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.