Viessmann · Boiler

F.365 Gas fitting relay monitoring has responded

High severity Vitocrossal 200 CI2

What the control is telling you

Burner is in a fault state.

Applies to: Vitocrossal 200 CI2

Likely causes

  • Gas fitting relay monitoring fault.

Test and repair steps

  1. Start the burner several times.
  2. Replace the burner control unit if the fault remains.

Models that show this code

21 models in Vitocrossal 200 CI2

100015002000399500750CI2 1000CI2 1500CI2 1500/2000CI2 2000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750

Other codes on the same units

  • F.1004 Reverse flow of flue gas in dry mode (CI2 1500/2000, partial load)
  • F.1061 Faulty BCU or faulty lead from O2 probe to BCU
  • F.1062 O2 controller and BCU measurements disagree
  • F.343 Short circuit, common return sensor (low loss header)
  • F.344 Lead break, common return sensor (low loss header)
  • F.347 Oxygen content fell below 0%: safety shutdown
  • F.364 Internal system fault
  • F.371 Fan speed not reached, below minimum speed

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 64. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.