Trane air conditioner error codes

78 codes (57 faults, 21 normal display and menu codes), plus 2 settings tables.

CodeMeaningSeverity / type
00Standby (A1000BA)Normal status
1st digit 0Standby (A1000AA)Normal status
1st digit 1Starting (A1000AA)Normal status
1st digit 2Low speed (A1000AA)Normal status
1st digit 3High speed (A1000AA)Normal status
1st digit 4Boost speed (A1000AA)Normal status
1st digit 5Limp mode (A1000AA)Normal status
1st digit 6Preheating (A1000AA)Normal status
1st digit 8De-rate (A1000AA)Normal status
1st digit 9Oil return (A1000AA)Normal status
2nd digit 1MOC fault (A1000AA board)High
2nd digit 2MOC communication fault (A1000AA board)High
2nd digit 3Compressor internal protection (IOL/OLP) (A1000AA board)High
2nd digit 4Compressor over-current protection (A1000AA board)High
2nd digit 5Outdoor fan over-current protection (A1000AA board)High
2nd digit 6High preheat IPM temperature (A1000AA board)High
2nd digit 7High coil temperature protection (A1000AA board)High
2nd digit 8High discharge temperature protection (A1000AA board)High
2nd digit 9High drive compressor IPM temperature (A1000AA board)High
2nd digit AOutdoor ambient sensor fault (A1000AA board)Medium
2nd digit CCoil temperature sensor fault (A1000AA board)Medium
2nd digit EHigh drive PFC temperature protection (A1000AA board)High
2nd digit FHigh drive fan IPM temperature protection (A1000AA board)High
2nd digit PPressure protection (high or low) (A1000AA board)High
2nd digit bAOC jumper pin engaged (A1000AA board)Medium
2nd digit dDischarge temperature sensor fault (A1000AA board)Medium
50Limp mode (A1000BA)Normal status
60Preheating (A1000BA)Normal status
d5De-rate: drive AC input over-currentMedium
d6De-rate: high drive IPM temperatureMedium
d7De-rate: high drive PFC temperatureMedium
d8De-rate: high coil temperatureMedium
E0Personality module errorHigh
E1Configuration errorHigh
E2AOC software / configuration mismatchHigh
F0AOC-MOC communication faultHigh
F1Compressor start-up faultHigh
F2Compressor over-currentHigh
F3Compressor control faultHigh
F4Outdoor fan control faultHigh
F5AC over-current faultHigh
F6Drive high temperature faultHigh
F7AC input voltage lowHigh
F8DC output voltage faultHigh
F9Drive (MOC) internal faultHigh
H5Hard lock: drive AC input over-currentCritical
H6Hard lock: high drive IPM temperatureCritical
H7Hard lock: high drive PFC temperatureCritical
H8Hard lock: high coil temperatureCritical
J1AOC FL jumper pin engaged (A1000BA)Normal status
J2.AOC FB jumper pin engaged (A1000BA)Normal status
L5Lockout: drive AC input over-currentHigh
L6Lockout: high drive IPM temperatureHigh
L7Lockout: high drive PFC temperatureHigh
L8Lockout: high coil temperatureHigh
Y1Running, low speed (A1000BA)Normal status
Y2Running, high speed (A1000BA)Normal status
Y2.Running, boost speed (A1000BA)Normal status
FAOutdoor ambient sensor faultMedium
FCCoil temperature sensor faultMedium
Fault history modeFault history diagnostics modeMenu / mode display
FdDischarge temperature sensor faultMedium
HCHard lock: compressor over-currentCritical
HFHard lock: outdoor fan over-currentCritical
HHHard lock: high pressure (HPCO / DTC)Critical
HLHard lock: low pressure (LPCO)Critical
HdHard lock: high discharge temperatureCritical
LCLockout: compressor over-currentHigh
LFLockout: outdoor fan over-currentHigh
LHLockout: high pressure (HPCO / DTC)High
LLLockout: low pressure (LPCO)High
LdLockout: high discharge temperatureHigh
Y.1Starting, low (A1000BA)Normal status
Y.2Starting, high (A1000BA)Normal status
btBoot (A1000BA)Normal status
dCDe-rate: compressor over-currentMedium
dFDe-rate: outdoor fan over-currentMedium
ddDe-rate: high discharge temperatureMedium

Settings and specs

Outdoor unit placement

Clearances · Trane 5TTR7

ItemValue
Above unit5 ft clear
Service side3 ft
Walls / shrubs12 in. min
Pad1 in. larger than unit all round, level, separate from house
Cold climate (HP)raise 3-12 in. above pad
Within 1 mile of salt wateradd BAYSEAC001 if no factory salt shield
Operating rangecooling 55-120 F, heating 0-66 F
  • Avoid bedroom walls and under roof drip lines.

Source: Trane ODR-SVN002E-EN (5TTR7/5TWR7) - Location Considerations / Table 1

Dimensions and weights

Specifications · Trane 5TTR7

ModelH x D x W (in.)Weight (lb)
5TWR7024A41 x 30 x 33181
5TWR7036A41 x 30 x 33194
5TWR7048A41 x 34 x 37231
5TWR7060A41 x 34 x 37241
5TTR7024A41 x 30 x 33176
5TTR7036A41 x 30 x 33189
5TTR7048A41 x 34 x 37226
5TTR7060A41 x 34 x 37236
  • Weights are estimated, uncrated.

Source: Trane ODR-SVN002E-EN (5TTR7/5TWR7) - Table 2

Models covered

5TTR7024A5TTR7036A5TTR7048A5TTR7060A

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.