Trane · Air conditioner
d5 De-rate: drive AC input over-current
What the control is telling you
Capacity reduced to limit input current. Manual lists only the meaning (A1000BA board); steps are general checks drawn from other sections of the guide.
Applies to: Trane 5TTR7 multi-speed AC (5TTR7024A-060A)
Likely causes
- Supply voltage out of range
- Voltage drop from loose or undersized wiring
- Drive fault
Test and repair steps
- Warning: After power off, wait 2 minutes - the inverter can hold 400 VDC. Confirm under 42 VDC at the +DC/-DC test points before touching the board.
- Measure incoming line voltage under load; compare with the nameplate range.
- Check the disconnect, breaker and wire size for voltage drop.
- Tighten all line connections at the drive.
Settings for these units
Outdoor unit placement · Trane 5TTR7
| Item | Value |
|---|---|
| Above unit | 5 ft clear |
| Service side | 3 ft |
| Walls / shrubs | 12 in. min |
| Pad | 1 in. larger than unit all round, level, separate from house |
| Cold climate (HP) | raise 3-12 in. above pad |
| Within 1 mile of salt water | add BAYSEAC001 if no factory salt shield |
| Operating range | cooling 55-120 F, heating 0-66 F |
Avoid bedroom walls and under roof drip lines.
Dimensions and weights · Trane 5TTR7
| Model | H x D x W (in.) | Weight (lb) |
|---|---|---|
| 5TWR7024A | 41 x 30 x 33 | 181 |
| 5TWR7036A | 41 x 30 x 33 | 194 |
| 5TWR7048A | 41 x 34 x 37 | 231 |
| 5TWR7060A | 41 x 34 x 37 | 241 |
| 5TTR7024A | 41 x 30 x 33 | 176 |
| 5TTR7036A | 41 x 30 x 33 | 189 |
| 5TTR7048A | 41 x 34 x 37 | 226 |
| 5TTR7060A | 41 x 34 x 37 | 236 |
Weights are estimated, uncrated.
Models that show this code
4 models in Trane 5TTR7
Other codes on the same units
- 2nd digit F High drive fan IPM temperature protection (A1000AA board)
- 2nd digit P Pressure protection (high or low) (A1000AA board)
- 2nd digit b AOC jumper pin engaged (A1000AA board)
- 2nd digit d Discharge temperature sensor fault (A1000AA board)
- d6 De-rate: high drive IPM temperature
- d7 De-rate: high drive PFC temperature
- d8 De-rate: high coil temperature
- E0 Personality module error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane ODR-SVN002E-EN (5TTR7/5TWR7 installer's guide) - section Integrated Variable Speed Control Board LED Indicators, Table 18 (A1000BA models). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.