Trane · Air conditioner
J1 AOC FL jumper pin engaged (A1000BA)
What the display is showing
Table lists the FL jumper engaged as a Run status with no fault entry.
Applies to: 5TTR7 A-C / 5TWR7 heat pump multi-speed outdoor drive (AOC)
Settings for these units
Outdoor unit placement · Trane 5TTR7
| Item | Value |
|---|---|
| Above unit | 5 ft clear |
| Service side | 3 ft |
| Walls / shrubs | 12 in. min |
| Pad | 1 in. larger than unit all round, level, separate from house |
| Cold climate (HP) | raise 3-12 in. above pad |
| Within 1 mile of salt water | add BAYSEAC001 if no factory salt shield |
| Operating range | cooling 55-120 F, heating 0-66 F |
Avoid bedroom walls and under roof drip lines.
Dimensions and weights · Trane 5TTR7
| Model | H x D x W (in.) | Weight (lb) |
|---|---|---|
| 5TWR7024A | 41 x 30 x 33 | 181 |
| 5TWR7036A | 41 x 30 x 33 | 194 |
| 5TWR7048A | 41 x 34 x 37 | 231 |
| 5TWR7060A | 41 x 34 x 37 | 241 |
| 5TTR7024A | 41 x 30 x 33 | 176 |
| 5TTR7036A | 41 x 30 x 33 | 189 |
| 5TTR7048A | 41 x 34 x 37 | 226 |
| 5TTR7060A | 41 x 34 x 37 | 236 |
Weights are estimated, uncrated.
Models that show this code
4 models in Trane 5TTR7
Other codes on the same units
- H5 Hard lock: drive AC input over-current
- H6 Hard lock: high drive IPM temperature
- H7 Hard lock: high drive PFC temperature
- H8 Hard lock: high coil temperature
- J2. AOC FB jumper pin engaged (A1000BA)
- L5 Lockout: drive AC input over-current
- L6 Lockout: high drive IPM temperature
- L7 Lockout: high drive PFC temperature
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane 5TTR7/5TWR7 installation ODR-SVN002E-EN, Table 18 A1000BA status/fault list, p.26-27. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.